Answer by ThreePhaseEel for 15 amp line connects to -> 20 amp line -> 20 amp...
The previous installer wired the bathroom GFCI backwardsThe symptom of a GFCI that shuts off power to downstream outlets but not itself when tested is a classic indication of a classic mistake. In...
View Article15 amp line connects to -> 20 amp line -> 20 amp GFCI -> 15 amp outlet
Regular 15amp non-GFCI breaker, first circuit stop is outdoor 15amp GFCI outlet, second stop is bathroom 20amp GFCI outlet, last stop is bathroom plain 15amp outlet. Everything is correctly wired.15a...